Effluent Treatment Plant with HRSCC for Textile Industry, India

Client: M/s. Parameshwari Textile (Exports) Private
Limited, India Location: India
Start Up: March 2012
Capacity: 400 m3/day

Description

Design, Engineering, Procurement, Construction, Installation, Commissioning, Testing, Technical assistance for Effluent treatment plant with High rate solid contact clarifier for textile industry in Tamilnadu, Southern India.

Technical Specifications

M/s. Prameshwari Textiles is setting up an Effluent treatment plant to treat 300 m3/day textile effluent water generated from various unit operations in the textile dyeing plant.

Effluent water generated in the textile plant was categorized into,

Dyeing Bath Water
Wash water

The above plant was designed to achieve BOD & COD lesser than 50 ppm and 100 ppm from 600 ppm and 1200 ppm respectively. According to APHA 21st EDN 2005 methods the BOD , COD and TDS measured as 5210 – B, 5220 – B and 2540 – C respectively.

Feed Pump – 22 m3/hr @ 2.5 kg/cm2
Equalization tank - Air blower – 372 m3/hr @ 0.5 kg/cm2
Primary HRSCC – 4.5 m dia x 3.5 HOS
Aeration tank blowers – 450 m3/hr @ 0.5 kg/cm2
Diffusers – 60 nos Retrievable type
Tube settler – 3.0 m x 3.0 m x 3.0 m
Thickener – 3.0 m dia x 3.0 m HOS
Belt filter press – 1.0 m3/hr